PARALLEL CONNECTION OF FUSE-LINKS TO INCREASE THE RATED CURRENT

Rules for parallel connection of fuse-links:

  • The fuse-links have to be the same type, size and rating.
  • The combination of parallel fuses must be selected by the manufacturer.
  • The current rating of parallel-connected fuse-links is lower than the sum of the single fuse-links (n x ln > ln parallel).
  • The current distribution on all parallel fuse-links must be the same.
  • Parallel fuse-links must be connected as prescribed by the manufacturer.
  • The incoming and outgoing connection must have prescribed cross-section.
  • The values of power dissipation are equal to the sum of values of power dissipation of a single fuse link.
  • The pre-arcing Joule integral is approximately equal to n2 x l2t(single fuse-link)
  • Breaking capacity is not larger than l1 of a single fuse-link.
  • The cut-off current is approximately equal n x lcut-off (single fuse-link)
  • The temperature rise of each parallel fuse-links is higher than the temperature rise of single fuse-link.